How Can We Help?
< All Topics
Print

Can you force a Bit of Word in PLC WorkShop for Siemens 505?

NO. X, Y, and C, which are discrete types, can be forced. WX and WY, which are Word types, can also be forced, but the individual bits cannot be forced separately. The 505 PLCs do not support this operation. Viewing the status of a WX or WY bit of word address in the Data Window or ladder may show the bit forced, but actual forcing can only happen if the complete word is forced.

Previous Can a program file created in the new version of WorkShop be opened with an older version of the software?
Next Do I still need to keep my COM Profibus configuration files?